Alarm List-71
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
6
The CIO parameter is
damaged.
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in
maintenance mode, and then load the data saved in the external
memory device.
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
7
The FD parameter is
damaged.
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in
maintenance mode, and then load the data saved in the external
memory device.
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy