Alar
m List
Alar
m Nu
mbe
r (4
00
0 to
4
9
99
)
Alarm List-481
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then insert the CF card which inserted original YCP21
board into the new YCP21 board.
201
An error occurred in the
semaphore of socket control
table of the Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then insert the CF card which inserted original YCP21
board into the new YCP21 board.
4131
UDP PROCESS
ERROR
1
An error occurred in the
creation of receiving socket
during the UDP process of the
Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then insert the CF card which inserted original YCP21
board into the new YCP21 board.
2
An error occurred in the
creation of transmission
socket during the UDP
process of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then insert the CF card which inserted original YCP21
board into the new YCP21 board.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy