Alarm List-81
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
0270
MEMORY ERROR
(CF BACKUP FILE)
The system software version
is inconsistent with the version
when the internal storage data
is set or the CompactFlash on
the YCP21 board is damaged.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
0280
MEMORY ERROR
(EX IO ALLOC FILE)
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in
maintenance mode, and then set the IO module.
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
0290
MEMORY ERROR
(NETWORK SETUP)
The network setting file is
damaged.
Data error
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in
maintenance mode, and then set the network again.
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YIF01
board, and then load the CMOS.BIN saved before alarm occurred.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy