Alarm List-86
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
20
Machine safety board save
data error
Setting error
(1)Select the following menu.
∙
[File]-[Initialize],[Machine Safety Board FLASH Reset]
(2)Turn the power OFF then back ON.
(3)If the alarm occurs again, select the following menu.
∙
[
File]-[Initialize]-[I/O Data],[YSF LOGIC FILE]
YSF21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YSF21
board, and then load the CMOS.BIN saved before alarm occurred.
YCP21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the following board. Save the
CMOS.BIN before replace the board to be safe.
∙
YCP21 board
YIF01 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the following board. Save the
CMOS.BIN before replace the board to be safe.
∙
YIF01 board
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
0301
VERIFY ERROR
(OVERRUN INPUT
SET)
Sub Code: Control group
Parameter specification and
OT signal information are
wrong
Setting error
(1)Check the following settings.
∙
Connection settings (OT) in maintenance mode
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy