Alarm List-51
EIP board failure
In the case of PCU-ETHIO(EtherNet/IP) board, please exchange with
the board which firmware version is correct.
PROFINET board failure
In the case of CP1616(PROFINET) board, please confirm the following
communication configuration using SIEMENS manufactured setting
tool (STEP 7). Please refer to the user manual of the CP1616 for more
information on how to set.
∙
When used as IO controller
- Download the project file.
∙
When used as IO device
- Assignment of IP address and device name. Factory reset before
performing the assignment.
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
19
An error was detected in
communications with the I/O
module board connected with
4th PCI when the control
power turned ON.
Setting error
(1)Check the following settings.
∙
PCI slot number in which each PCI board is mounted
∙
I/O module settings in maintenance mode
Please refer to the manual of each IO module for the details of the
setting.
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
∙
The PCI connector of the corresponding I/O module
I/O module failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the following board. Save the
CMOS.BIN before replace the board to be safe.
∙
The corresponding I/O module (PCI board)
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy