DK424 Installation
Reserve Power Installation
5-32
Strata DK I&M 6/00
Reserve Power Installation
Two or four customer-supplied, 12VDC batteries (80 amp hours maximum) can be connected to
the system as a power failure backup. In the event of a power failure, the system automatically
switches over to battery power without any interruption to existing calls or other normal system
functions.
The length of time reserve power operates depends on the system, size and number of batteries
provided, and the system load. Typical reserve power duration estimates and battery specifications
are estimated with the following considerations (see
♦
Batteries have full charge at start of operation.
♦
Two or four batteries connected per
♦
Batteries are 12VDC, rated at 80 amp/hours each.
♦
System is operating at full load traffic with LCD phones.
♦
Batteries used for this test are gel-cell and maintenance-free. Reserve duration will vary
depending upon battery type, age, and manufacturer. These figures should only be used as an
estimate.
Table 5-4
Typical Reserve Power Duration Estimate
The procedure for installing reserve power varies, depending on the number of cabinets in the
system and the mounting method employed in installing the cabinets. The following text details
reserve power battery installation requirements.
Number of Cabinets
1
2
3
4
5
6
7
Estimated operation time
Two-battery configuration
16.0 hr
8.0 hr
5.0 hr
3.7 hr
3.0 hr
2.5 hr
0.5 hr
Estimated operation time
Four-battery configuration
32.0 hr
16.0 hr
10.0 hr
7.5 hr
6.0 hr
5.0 hr
2.0 hr
DC Current Drain (-24 VDC)
3.5 amps
6.7 amps
9.9 amps
13.1 amps
16.3 amps
19.5 amps
22.7 amps
AC Input Current (AC Current
Limitation by National
Electric Code)
2.5 amps
5.0 amps
7.5 amps
10.0 amps
11.5 amps
15.0 amps
17.5 amps
WARNING!
Some batteries can generate explosive gases. Therefore...
Ensure that batteries are located in a well-ventilated area.
Do not smoke near batteries.
Avoid creating any electrical sparks near batteries.
Use commercially available battery enclosures to reduce risk to
nearby people and equipment.
WARNING!
Battery cables that exit the cabinet(s) are not UL listed because of
possible incorrect installations. Have a licensed electrician install these
cables.
Содержание Strata AirLink DK40i
Страница 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Страница 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Страница 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Страница 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Страница 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Страница 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Страница 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Страница 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Страница 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...