RDRE1.Health
Information
Device Healthy
0
1
RDRE1.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
RDRE1.RcdMade
Information
Fault Record ready for Download
0
RDRE1.RcdMade.StVal
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
FALSE: 0
TRUE: 1
RDRE1.FltNum
Information
Fault Record Number
Integer
RDRE1.FltNum.StVal
Value
RDRE1.GriFltNum
Information
Fault Record Number
Integer
RDRE1.GriFltNum.StVal
Value
Fault Storage
Records are triggered from operation of an output relay programmed as a
Trip Contact
Trip Alert
feature must also be enabled, (see
).
Measured quantities for the last 100 relay trip fault records are stored with time and date of trip. Fault data
records can be viewed on the HMI LCD. These include the LED status at the time of recording.
Fault records are stored in a rolling buffer. When the buffer is full the oldest faults are overwritten.
The functionality is configured in the
Configuration > Data Storage > Fault Storage
menu.
3.6.3
Device Functionality
3.6 Data Storage
114
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...