Parameter:
24IT Reset
•
Default setting: 0 s
The reset time delay is initiated when the measured fluxing value falls below the pickup level.
The stored flux level is reset to zero after elapse of the rest time.
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
24 V/f
Enabled
Disabled
Disabled
Functions > Protection > 24 > 24DT-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.1 to 2 p.u., Δ 0.01 p.u.
1.10
p.u.
Hysteresis
0 to 80 %, Δ 1 %
0.1 %
Delay (DTL)
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
20 s
Functions > Protection > 24 > 24IT-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Reset
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 10 s
0 s
X0 Point
1 to 2 p.u., Δ 0.01 p.u.
1.1 p.u.
Y0 Point
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
20000 s
X1 Point
1 to 2 p.u., Δ 0.01 p.u.
1.14
p.u.
Y1 Point
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
1200 s
X2 Point
1 to 2 p.u., Δ 0.01 p.u.
1.16
p.u.
5.2.5
Protection and Automation Functions
5.2 24 Overexcitation Protection
154
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...