Element Blocking
The Vx Under Voltage elements can be blocked by
Binary Input Inhibit
. This functionality should be
checked.
Element
BI Inhibits
27-1
27-2
Check correct indication, trip output, alarm contacts, waveform record.
When testing is complete reinstate any of the disabled functions.
Undervoltage Guard
If any Vx undervoltage element is set to be inhibited by the
UV Guard
element, this function should be
tested.
Connect the test voltage inputs to suit the installation wiring diagram utilizing any test socket facilities avail-
able. It may be useful to temporarily map an LED as
General Pickup
to assist during testing.
UV Guard
operation will reset the
General Pickup
if no other element is operated. This LED should not be set as
Hand Reset
in the output matrix.
Starting from nominal voltage, apply a step decrease to the applied voltage to a level below the 27Vx under-
voltage setting but above the 27Vx
UV Guard
setting such that an undervoltage element operation occurs.
Slowly reduce the applied voltage until the 27Vx undervoltage element resets, this can be detected by the
General Pickup
LED reset if no other element is operated (this includes any undervoltage element which is
not UV guarded).
Phase
Setting (Volts)
Tolerance
V Element Used
for Test
Blocked Volts
Notes
Vx UVG
37 Undercurrent Protection – Phase
If 2 undercurrent 37 elements are used with different settings, it is convenient to test the element with the
lowest setting first. The higher setting element can then be tested without interference from the other
element.
Apply 3 phase balanced current at a level above the undercurrent 37-n setting until the element resets.
Reduce single phase current to below setting to prove the operation of the
Pickup Option Any/All
setting.
If DTL setting is small, gradually reduce single phase current or 3 phase currents until element operates.
If DTL is large apply 1.1 times setting, check for no operation, apply 0.9 times setting, check operation.
Testing of this element phase by phase may cause inadvertent operation of the 46 NPS overcurrent elements.
Apply 0.5 times setting current and record operating time.
Phase
I
set
(Amps)
DTL (sec)
P.U. Current
Amps
Tolerence
Op. Time 0.5 ⋅
I
set
Tolerance
CT1(I
A
)
CT2(I
B
)
CT3(I
C
)
Element Blocking
The undercurrent elements can be blocked by
Binary Input Inhibit
. This functionality should be
checked.
9.10.5
Functional Tests
9.10 Protection Functional Tests
Reyrolle 7SR5, Transformer Protection Device, Device Manual
425
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...