Function Configuration
Overview of the Function
Each installed function group (FG) in the device can be enabled or disabled in this menu. All available function
elements (FE) for the relevant FG can also be individually enabled or disabled from within the specific FE
settings group.
Structure of the Function
The
Function Config
has group dependent settings. These settings can be different in each settings group
– group numbers (Gn) 1 to 4.
Logic of the Function
[lo_7SR5_FunctionConfigurationlogicdiagram, 1, en_US]
Figure 4-5
Logic Diagram: Function Group and Function Element Enable/Disable
Application and Setting Notes
•
Parameter:
Function Enable/Disable
Default setting:
Disabled
When set to disabled all instances of the relevent function element are disabled. When set to enabled the
individual instances of the function elements can be enabled – see individual function described in
sections 5, 6, and 7.
Settings Menu
Settings > Functions > Function Config
Function Group
Range
Settings
Default
Gn1
Gn2
Gn3
Gn4
21LB Load blinder
Enabled
Disabled
Disabled
24 Overexcitation
Protection
Enabled
Disabled
Disabled
27 Undervoltage
Enabled
Disabled
Disabled
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.5
7SR54 Function Templates
4.3 Function Configuration
Reyrolle 7SR5, Transformer Protection Device, Device Manual
139
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...