Settings Menu
Functions > Protection > 60VTS
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Component
NPS
ZPS
NPS
V
7 to 110 V, Δ 1 V
7 V
I
0.05 to 1 ⋅ I
rated
, Δ 0.05 ⋅ I
rated
0.1 ⋅
I
rated
V
PPS
15 to 110 V, Δ 1 V
15 V
I
PPS
Load
0.05 to1 ⋅ I
rated
, Δ 0.05 ⋅ I
rated
0.1 ⋅
I
rated
I
PPS
Fault
0.05 to 20 ⋅ I
rated
, Δ 0.05 ⋅
I
rated
10 ⋅ I
rated
Delay (DTL)
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
10 s
Information List
Input/Output Matrix
General
Pickup
User Logic
Type
Serial
Protocol
Inhibit 60VTS
Inhibit 60VTS
Input
60VTS
60VTS Operated
Output
Y
60VTS Pickup
Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
6.3.5
6.3.6
Supervision Functions
6.3 60VTS VT Supervision
354
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...