Functions > Protection > 50 > Gn 50-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Dir. Control
7
Non-Dir
forward
reverse
Non-Dir
Setting
0.05 to 2.5 I
rated
, Δ 0.01 I
rated
2.55 to 25 I
rated
, Δ 0.05 I
rated
25.5 to 50 I
rated
, Δ 0.5 I
rated
1 ⋅ I
rated
Delay
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
VTS Action
7
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit
No
Yes
No
79 Delayed Inhibit
No
Yes
No
21LB-3P Inhibit
7
No
Yes
No
21LB-1P Inhibit
7
No
Yes
No
IEC 61850 Functional Information Mapping
A50PTOC*.Mod
Information
50 Overcurrent Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A50PTOC*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
5.11.6
7
Applies only to devices with VT inputs
Protection and Automation Functions
5.11 50 Instantaneous Overcurrent – Phase
210
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...