Functions > Protection > 51G > Gn 51G-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Delay (DTL)
0 to 20 s Δ 0.01 s
5 s
Min Operate Time
0 to 20 s Δ 0.01 s
0 s
Follower DTL
0 to 20 s Δ 0.01 s
0 s
Reset
IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
9
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit
No
Yes
No
79 Delayed Inhibit
No
Yes
No
IEC 61850 Functional Information Mapping
A51GPTOC*.Mod
Information
51G Earth Fault Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A51GPTOC*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A51GPTOC*.Health
Information
Device Healthy
0
1
A51GPTOC*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
5.15.6
Protection and Automation Functions
5.15 51G Time-Delayed Earth Fault – Measured
Reyrolle 7SR5, Transformer Protection Device, Device Manual
253
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...