Parameter:
Select Grp Mode
•
Default Setting:
Edge Triggered
This setting is applicable when an assigned binary input is used to select a settings group. See
Input
Config > Input Matrix > Select Group n
.
When operated the active settings group can be set to 1 (Gn1), 2 (Gn2), 3 (Gn3) or 4 (Gn4). The select
group mode is defined as follows:
Level triggered: the selected settings group is operational only whilst the input is energized.
Edge triggered: the selected settings group is enabled by the leading edge of the binary input operating
pulse and remains latched in regardless of the status of the binary input.
i
i
NOTE
Only 1 group should be energized at any time. If a second group is selected simultaneously the second
selection is ignored, even if the first subsequently resets. When a level triggered selection is reset, the relay
will return to the previously active group.
Parameter:
Operating Mode
•
Default Setting:
Local or Remote
Table 3-2
Operation Mode
Operation
Remote
Local
Out of Service
Control
Rear RS485 port (set as
Remote
)
Enabled
Disabled
Disabled
Rear RS485 port (set as
Local
)
Disabled
Enabled
Disabled
Rear ethernet ports (set as
Remote
)
Enabled
Disabled
Disabled
Rear ethernet ports (set as
Local
)
Disabled
Enabled
Disabled
Fascia (Control mode)
Disabled
Enabled
Disabled
Front USB port (set as
Remote
)
Enabled
Disabled
Disabled
Front USB port (set as
Local
)
Disabled
Enabled
Disabled
Control and test reset– Fascia
Enabled
Disabled
Disabled
Binary inputs (set as
Enabled in Remote
)
Enabled
Disabled
Disabled
Binary inputs (set as
Enabled in Local
)
Disabled
Enabled
Disabled
Binary inputs (set as
Out of Service
)
Disabled
Disabled
Enabled
Binary outputs
Enabled
Enabled
Disabled
Mimic Screen Controls
Reporting
Spontaneous
IEC 60870-5-103
Enabled
Enabled
Disabled
DNP3
Enabled
Enabled
Disabled
General Interrogation
IEC 60870-5-103
Enabled
Enabled
Disabled
DNP3
Enabled
Enabled
Enabled
MODBUS
Enabled
Enabled
Enabled
Changing of settings
Rear RS485 port (set as
Remote
)
Enabled
Disabled
Enabled
Rear RS485 port (set as
Local
)
Disabled
Enabled
Enabled
Device Functionality
3.2 Device Configuration
50
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...