Interposing CT Selection Guide – Power Trans-
former Vector Group
W1 ICT Connection
W2 ICT Connection
Yd3, YNd3 + Earthing Transformer
Yd3,-90°
Ydy0,0°
Yy4, YNy4, Yyn4, YNyn4, Ydy4, YNdy4, Ydyn4,
Yndyn4, Dz4
Ydy4,-120°
Ydy0,0°
Yd5, YNd5
Yd5,-150°
Yy0,0°
Yd5, YNd5 + Earthing Transformer
Yd5,-150°
Ydy0,0°
Yy6, YNy6, Yyn6, YNyn6, Ydy6, YNdy6, Ydyn6,
Yndyn6, Dz6
Ydy6,180°
Ydy0,0°
Yd7, YNd7
Yd7,150°
Yy0,0°
Yd7, YNd7 + Earthing Transformer
Yd7,150°
Ydy0,0°
Yy8, YNy8, Yyn8, YNyn8, Ydy8, YNdy8, Ydyn8,
Yndyn8, Dz8
Ydy8,120°
Ydy0,0°
Yd9, YNd9
Yd9,90°
Yy0,0°
Yd9, YNd9 + Earthing Transformer
Yd9,90°
Ydy0,0°
Yy10, Yny10, Yyn10, YNyn10, Ydy10, YNdy10,
Ydyn10, Yndyn10, Dz10
Ydy10,60°
Ydy0,0°
Yd11, Ynd11
Yd11,30°
Yy0,0°
Yd11, Ynd11 + Earthing Transformer
Yd11,30°
Ydy0,0°
Dy1, Dyn1
Yy0,0°
Yd11,30°
Dy1, Dyn1 + Earthing Transformer
Ydy0,0°
Yd11,30°
Dy3, Dyn3
Yy0,0°
Yd9,90°
Dy3, Dyn3 + Earthing Transformer
Ydy0,0°
Yd9,90°
Dy5, Dyn5
Yy0,0°
Yd7,150°
Dy5, Dyn5 + Earthing Transformer
Ydy0,0°
Yd7,150°
Dy7, Dyn7
Yy0,0°
Yd5,-150°
Dy7, Dyn7 + Earthing Transformer
Ydy0,0°
Yd5,-150°
Dy9, Dyn9
Yy0,0°
Yd3,-90°
Dy9, Dyn9 + Earthing Transformer
Ydy0,0°
Yd3,-90°
Dy11, Dyn11
Yy0,0°
Yd1,-30°
Dy11, Dyn11 + Earthing Transformer
Ydy0,0°
Yd1,-30°
(1)
Y or y denotes an unearthed star connection on the HV or LV side of the transformer.
(2)
YN or yn denotes an earthed star connection on the HV or LV side of the transformer.
(3)
D or d denotes a delta connection on the HV or LV side of the transformer respectively.
(4)
Z or z denotes a zigzag connection of the HV or LV side of the transformer respectively.
Parameter:
Gn 87T Common > Wn 87T Zone Inputs
•
Default setting:
<all>
This specifies the CT winding inputs used by the differential protection.
Parameter:
Gn 87T Common > Wn 87T-HB Select
•
Default setting:
Operate
The differential current inrush blocking can be derived from the differential (operate) circuit (87T-HB2) or
measured directly from the line CT inputs (81HB2).
Protection and Automation Functions
5.22 87T Transformer Differential Protection
314
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...