IEC 61850 Functional Information Mapping
Voltage Operated Binary Inputs
BIGGIO1.Mod
Information
Reset Device
x
BIGGIO1.Mod.stVal
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
BIGGIO1.Health
Information
Device Healthy
0
1
BIGGIO1.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
BIGGIO1.Ind*
Information
Binary I/P* Status
0
1
BIGGIO1.Ind*.stVal
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
* Values of 1 to max number of BI.
IEC 61850 Value
ON: 1
OFF: 0
3.4.6
Device Functionality
3.4 Binary Inputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual
75
C53000-G7040-C015-1, Edition 11.2019