Parameter:
Reset CB-n Trip Time
•
Default Setting:
<None>
This resets the CB trip time instrument i.e. the measured time between the trip being issued and detec-
tion of the CB open state, (see
, section 52 Circuit-Breaker Control).
Parameter:
General Alarm n
•
Default Setting:
Alarm n (n = 1 to 20)
In the
Binary Inputs > General Alarms
menu user defined text can be entered for alarm condi-
tions e.g.
Buchholz Gas
. When a binary input programmed to
General Alarm n
is operated the user
text is displayed on the fascia LCD.
This display can be disabled, (see
Configuration > Device > General Alarm Alert
).
Parameter:
Trig Trip Contacts
•
Default Setting:
<None>
This setting is used to operate output relays assigned as
Binary Outputs > Trip Config > Trip
Contacts
. This will also initiate operation of the functionality associated with trip contacts, (see
Parameter:
Trigger Fault Rec
•
Default Setting:
This setting is used to trigger the fault recorder on demand.
Parameter:
Trigger Wave Rec
•
Default Setting:
<None>
This setting is used to trigger the waveform recorder on demand. Typically this is triggered on circuit
switch using a binary input operated from a CB auxiliary switching or during periods of maintenance/
monitoring testing.
Parameter:
Select Group n (n = 1 to 4)
•
Default Setting:
<None>
This setting switches the device settings to the nominated settings group number (Gn). The nominated
settings group is active depending on the behavior of the
Select Group Mode
function, (see
Config-
uration > Device > Select Grp Mode
):
Level triggered
: the selected settings group is operational as long as the input is energized.
Edge triggered
: the selected settings group is enabled by the leading edge of the binary input oper-
ating pulse and remains latched in regardless of the status of the binary input.
Parameter:
Clock Sync
•
Default Setting:
<None>
The device real time clock is set to the nearest second when the binary input is operated i.e. on pickup.
Parameter:
Reset Start Count
•
Default Setting:
<None>
See
Device Functionality
3.4 Binary Inputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual
71
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...