Application and Setting Notes
Parameter:
24DT Setting
•
Default setting:
1.10 p.u.
The recommended setting is below the over-fluxing withstand capacity of the protected plant.
The setting is for a multiple of per-unit flux (V/f), where:
1 p.u. (V/f) = VT rated secondary voltage (nominal) / Rated Frequency (System frequency)
Parameter:
24DT Hysteresis
•
Default setting:
0.1 %
The recommended setting is the feasible upper limit selected to avoid output chattering for marginal
measured values.
Parameter:
24DT Delay
•
Default setting:
60 s
The time delay is set below the over-fluxing withstand capability of the protected plant at the operate
setting.
5.2.4
Protection and Automation Functions
5.2 24 Overexcitation Protection
152
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019