Control and Logic Functions
Quick Logic
If this functionality is used, the logic equations may interfere with testing of other protection functions in the
relay. The function of the
Quick Logic
equations should be tested conjunctively with connected plant or by
simulation to assess suitability and check for correct operation on an individual basis with tests specifically
devised to suit the particular application.
9.12
9.12.1
Functional Tests
9.12 Control and Logic Functions
454
Reyrolle 7SR5, Transformer Protection Device, Device Manual