Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
50N Earth Fault
Enabled
Disabled
Disabled
Functions > Protection > 50N > Gn 50N-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Measurement
RMS
Fundemental
RMS
Dir. Control
Non-Dir
forward
reverse
Non-Dir
Setting
0.05 to 2.5 I
rated
, Δ 0.01 I
rated
2.55 to 50 I
rated
, Δ 0.5 I
rated
0.5 ⋅
I
rated
Delay (DTL)
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
VTS Action
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit
No
Yes
No
79 Delayed Inhibit
No
Yes
No
IEC 61850 Functional Information Mapping
A50NPTOC*.Mod
Information
50N Earth Fault Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A50NPTOC*.Mod.stVal
5
5
2
1
5.13.5
5.13.6
Protection and Automation Functions
5.13 50N Instantaneous Earth Fault – Calculated
Reyrolle 7SR5, Transformer Protection Device, Device Manual
225
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...