Parameter:
79 Delayed Inhibit
•
Default setting:
No
The autoreclose scheme can be designed such that only instantaneous elements are used for the first
trip(s) of the sequence before reverting to time graded protection. This setting allows the delayed
element to be inhibited during the delayed autoreclose shots and should be left at the default setting of
Off
unless this is required.
Note that function elements are assigned as
Delayed Trips
in the
79 > 79PF
menu.
Parameter Value
Description
No
The element is not inhibited by the autoreclose sequence design.
Yes
The element will be inhibited during any autoreclose shot which is designated as
delayed. Incorrect configuration can result in no protection being enabled.
Settings Example
There should be little or no current flowing to earth in a healthy system so earth fault relays can be given far
lower pickup levels than relays which detect excess current above load current in each phase conductor. Earth
fault relays are important where the fault path to earth is a high-resistance one (such as in highly arid areas) or
where the system uses high values of earthing resistor/reactance as any earth fault current that flows in the
phase conductors will be limited.
Settings Menu
Configuration > Function Config
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
51N Earth Fault
Enabled
Disabled
Disabled
Functions > Protection > 51N > Gn 51N-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Dir. Control
10
Non-Dir
Forward
Reverse
Non-Dir
Setting
0.05 to 2.5 ⋅ I
rated
, Δ 0.05
I
rated
0.5 ⋅
I
rated
Char
DTL
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-EI
ANSI-MI
ANSI-VI
IEC-NI
5.16.5
10
Applies only to devices with VT inputs.
Protection and Automation Functions
5.16 51N Time-Delayed Earth Fault – Calculated
260
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...