Parameter:
Binary Outputs > Trip Config > Trip Contacts
•
Default Setting:
<None>
Operation of the specified contacts are identified as those that are used to trip a circuit‑breaker.
Operation of any binary output assigned as a
Trip Contact
will trigger storage of a
Fault Data
Record
, actuate the
Trip Alert
screen (when
System Config > Trip Alert = Enabled
) and
initiate the
CB Fail
protection sequence (when enabled).
Parameter:
Binary Outputs > Trip Config > Trip Triggered
•
Default Setting:
<None>
Operation of the selected LEDs or virtual I/Os is initiated when a binary input configured as a
Trip
Contact
operates. This provides a logic signal from the trip signal that can be used to provide indication
that a trip has occured.
i
i
NOTE
Where the
Trip Triggered
is not configured then the
Trip Alert
and
Fault Records
will not be
triggered.
Device Functionality
3.5 Binary Outputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual
83
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...