59N Neutral Voltage Displacement
Common Settings
Reference
Parameter
Value
Input selection
VN, VT4
Definite Time Element (59NDT)
Reference
Parameter
Value
V
set
Setting
1 to 100 V
V
Applied voltage (for operate time)
0 to 2 ⋅ V
set
(switched)
0 to 10 ⋅ V
set
(switched)
t
delay
Delay setting
0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute
Value
V
op
Operate level
V
set
: ± 2 % or ± 0.5 V
Reset level
≥ 95 % V
op
or ± 0.5 V
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
1.5 ⋅ V
set
: 76 ms ± 20 ms
10 ⋅ V
set
: 63 ms ± 20 ms
t
op
Operate time following delay
t
basic
+ t
delay
± 1 % or ± 20 ms
Repeatability
± 1 % or ± 20 ms
Overshoot time
< 80 ms
Disengaging time
< 100 ms
Inverse Time Element (59NIT)
Reference
Parameter
Value
Tm
Time multiplier setting
0.1 to 140
V
set
Setting
1 to 100 V
10.20
10.20.1
10.20.2
10.20.3
Technical Data
10.20 59N Neutral Voltage Displacement
486
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...