Parameter:
Setting
•
Default setting: 1 x I
n
(1 ⋅ I
rated
)
This setting defines the operating current threshold of the element. The measured earth current must
exceed this setting by a factor of 1.05 for pickup of the element. The operation timing will then be
dependent on the selected characteristic for the element setting. The element pickup will reset when the
current is reduced by 0.97 the setting and the reset characteristic will be applied. This factor is always
applied for 51 elements including when the
Char
is selected as DTL.
This setting should be set to suit the individual application.
Parameter:
Char
•
Default setting:
IEC NI – IEC normal inverse
This setting defines the characteristic of the inverse curve. Standard ANSI and IEC curves are provided as
standard. The characteristic curves and associated formulas are shown in
Custom (user defined) curves can be configured in Reydisp Manager and added to the device configura-
tion. The custom curve will appear as an additional option in the
Char
setting list using the name that is
entered in Reydisp Manager for all elements for which the curve is applicable.
The characteristic can also be set as DTL, see
51G-n Delay
,
The characteristic should be set to suit the individual application.
Parameter:
Time Mult
(IEC/ANSI)
•
Default setting:
1
This setting defines the time multiplier that is applied to the selected current curve. For IEC curves this
value is traditionally in the range 0 to 1.6 and for ANSI curves a value of 0 to 15 is typically applied.
Parameter:
Delay
(DTL)
•
Default setting:
0.1 s
This is the time delay setting for the element when the
Char
is selected as DTL. This should be set to suit
the individual application. This setting is not used if any other characteristic curve is selected.
Protection and Automation Functions
5.15 51G Time-Delayed Earth Fault – Measured
Reyrolle 7SR5, Transformer Protection Device, Device Manual
249
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...