37 Undercurrent Protection – Phase
Common Settings
Reference
Parameter
Value
I
set
UC guard setting
0.05 to 5 ⋅ I
rated
, Δ 0.05
I
Applied current (for operate time)
1.1 to 0.5 ⋅ I
set
(switched)
Operate and Reset Level
Attribute
Value
I
op
Operate level
I
set
: ± 5 % or ± 1 % I
rated
Reset level
≤ 105 % I
op
± 1 %
t
op
Operate time
0.5 ⋅ I
set
: 35 ms, ± 10 ms
Reset time
Undercurrent Protection
Reference
Parameter
Value
I
set
Setting
0.05 to 5 ⋅ I
rated
,Δ 0.05
I
Applied current (for operate time)
1.1 to 0.5 ⋅ I
set
(switched)
t
delay
Delay setting
0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute
Value
I
op
Operate level
I
set
: ± 5 % or ± 1 % I
rated
Reset level
≤ 105 % I
op
or I
op
± 1 % I
rated
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
0.5 ⋅ I
set
: 50 ms ± 10 ms
t
op
Operate time following delay
t
basic
+ t
delay
± 1 % or ± 10 ms
Repeatability
± 1 % or ± 10 ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
10.6
10.6.1
10.6.2
Technical Data
10.6 37 Undercurrent Protection – Phase
Reyrolle 7SR5, Transformer Protection Device, Device Manual
463
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...