Parameter:
VT1/2/3 Ratio Sec
•
Default setting:
110 V
The setting value is used (in conjunction with
VT1/2/3 Ratio Prim
setting) by the device instrumen-
tation e.g. to display primary voltage values.
Parameter:
VT1/2/3 Nominal
•
Default setting:
63.5 V
This is set to the rated voltage applied to the VT input. The setting will be dependent on the
VT Config
setting e.g. phase-phase or phase-neutral Volts may be connected to the VT inputs.
Parameter:
VT1/2/3 Trim Magnitude
•
Default setting:
0 V
The setting value is used (in conjunction with
VT1/2/3 Ratio Prim
setting) by the device instrumen-
tation e.g. to display primary voltage values.
Parameter:
VT1/2/3 Trim Angle
•
Default setting:
0°
The setting value is used (in conjunction with
VT1/2/3 Ratio Prim
setting) by the device instrumen-
tation e.g. to display primary voltage values.
Parameter:
VT1/2/3 Config
•
Default setting:
Van, Vbn, Vcn
This setting provides the device with the correct voltage inputs i.e. provides inputs configuration appro-
priate to the switchgear VT connections. The VT connections and required settings are illustrated in
Note that the switchgear VT connection may affect the functionality that can be used in the device on the
system e.g. The VT1/2/3 configuration Va, Vb, Vc in
does not allow zero sequence voltage V
0
to
be measured and so functions requiring this quantity cannot be used when this VT configuration is
selected.
Parameter:
VT4 Nominal
•
Default setting:
63.5 V
This is set to the rated voltage applied to the VT input. The setting will be dependent on the
VT Config
setting e.g. phase-phase or phase-neutral Volts may be connected to the VT inputs.
Parameter:
VT4 Ratio Prim
•
Default setting:
132000 V
The setting value is used (in conjunction with
VT1/2/3 Ratio Sec
setting) by the device instrumenta-
tion e.g. to display primary voltage values.
Parameter:
VT4 Ratio Sec
•
Default setting:
110 V
The setting value is used (in conjunction with
VT1/2/3 Ratio Prim
setting) by the device instrumen-
tation e.g. to display primary voltage values.
Device Functionality
3.3 CT and VT Inputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual
61
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...