Element Blocking
The Vx overvoltage elements can be blocked by
Binary Input Inhibit
. This functionality should be
checked.
Element
BI Inhibits
59Vx-1
59Vx-2
Check correct indication, trip output, alarm contacts, waveform record.
When testing is complete reinstate any of the disabled functions.
67 Directional Overcurrent – Phase
If the relay has
Directional Overcurrent
elements, the common direction polarizing can be checked
independently from the individual overcurrent elements and their settings. If
Phase Rotation ACB
is
selected in the CT/VT menu, this corresponds to negative phase sequence and the
Forward
and
Reverse
will
be automatically exchanged by internal relay configuration. The tests below describe normal ABC rotation and
the forward/reverse direction reversal will be experienced for ACB settings unless single phase voltages are
inverted. Directions for 3 phase testing will also be reversed unless the 3 phase supply rotation is reversed.
This can be achieved by swapping any 2 phase wires, for both current and voltage with a standard ABC test
supply.
Direction Earth Fault
direction is not affected by the
Phase Rotation
direction.
In the
Instruments
mode display, indication is provided in the
Directional Meters
menu which
displays current direction under P/F Dir as forward or reverse based on the output states of the directional
elements, i.e. whether they see forward current, reverse current or neither for each pole with respect to the
67
Char Angle
setting in the
Phase Overcurrent
menu. This display and the equivalent
Measured
and
Calculated Earth Fault
direction meters can be used as an aid to commissioning testing.
1. Check the direction of each pole in turn by connecting to the appropriate terminals. The following table
shows the polarizing quantity for each pole.
Table 9-8
Connections for Directional Polarity
Overcurrent Pole
Polarizing Voltage
Phase A
V
BC
Phase B
V
CA
Phase C
V
AB
2. Inject single phase rated current and apply single phase-phase rated voltage at the
Char Angle
(MTA)
phase angle setting, to each phase in turn. For each pole, monitor the directional display in the instrument
menu and check that indication of forward current (FWD) is displayed. To achieve the required forward charac-
teristic angle, the phase angle of the current should be greater than that of the polarizing voltage by the angle
setting.
3. Repeat all of the above with the current connections reversed. Indication should now be given of reverse
(REV) current flow.
Phase
A
B
C
Forward
FWD
FWD
FWD
Reverse
REV
REV
REV
4. Apply balanced 3 phase rated voltage and current with V
BC
voltage as a 0° reference and I
a
at the character-
istic angle. Increase current phase angle until the
Fwd
indication is extinguished. Record this angle in the table
below (Forward lead DO). Continue to increase/decrease the angle until the instrument reads
Rev
. Record the
angle (Reverse lead PU). Reduce the current angle until the
Rev
extinguishes (Reverse lead DO). and the
Fwd
subsequently returns (Forward lead PU), recording the angles. Repeat the above tests, starting from the
Characteristic Angle
, but reducing the current phase angle to record the directional boundaries in the
opposite (lag) direction. The recorded angle should be the angle at which the phase current leads the phase-
9.10.19
Functional Tests
9.10 Protection Functional Tests
Reyrolle 7SR5, Transformer Protection Device, Device Manual
443
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...