Parameter:
Enabled in Local
•
Default Setting:
<All>
Operation of the selected binary input is enabled when
Device Config > Operating Mode
is
selected to
Local
, (see
).
Parameter:
Enabled in Remote
•
Default Setting:
<All>
Operation of the selected binary input is enabled when
Device Config > Operating Mode
is
selected to
Remote
, (see
).
Parameter:
Enabled in Out of Service
•
Default Setting:
<All>
Operation of the selected binary input is enabled when
Device Config > Operating Mode
is
selected to
Out of Service
, (see
Parameter:
Inhibit <Function>
•
Default Setting:
<None>
When operated the binary input initiates the reset sequence of the relevant function element(s).
Parameter:
Ext Trig 60VTS
•
Default Setting:
<None>
Used to initiate the VT supervision function (60VTS) time delay element from a MCB connected in the VT
secondary circuit, (see
, section 60VTS VT Supervision).
Parameter:
Ext Reset 60VTS
•
Default Setting:
Used to reset the VT supervision function (60VTS) when a VT failure condition no longer exists, (see
, section 60VTS VT Supervision).
Parameter:
50BF-n CB Faulty
•
Default Setting:
<None>
This input is connected to the CB monitoring circuits. If this input is operated when a trip initiation is
received an output will be given immediately (the timers are by passed), (see
section 50BF Circuit-Breaker Failure Protection – 3 Pole).
Parameter:
50BF-n Mech Trip
•
Default Setting:
<None>
Used to trigger the circuit‑breaker fail function. A binary input configured as
CB Closed
must also be
energized to confirm CB failure, (see
, section 50BF Circuit-Breaker Failure
Protection – 3 Pole).
Device Functionality
3.4 Binary Inputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual
69
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...