Device Configuration
Overview of Functions
The device configuration parameters are used to parameterize selected basic operating functionality of the
device.
The Reydisp Manager PC tool is used to configure the device.
Structure of the Function
The settings applied here are common to all function element settings groups i.e. settings group 1 (Gn1) to
settings group 4 (Gn4).
The device configuration covers a number of operating modes including:
•
Power system rated frequency
•
Display operating modes including settings, meters, fault and alarm alerts
•
Time setting and methods of time synchronizing
•
Local, remote and in-service operating modes
•
User identification
Logic of the Function
[lo_7SR5_DeviceConfiguration_OperatingMode, 1, en_US]
Figure 3-3
Device Configuration > Operating Mode
Application and Setting Notes
Parameter:
System Frequency
•
Default Setting:
50 Hz
This setting is selected to be equal to the power system rated frequency.
i
i
NOTE
Changing the parameter will cause the device to restart.
3.2
3.2.1
3.2.2
3.2.3
3.2.4
Device Functionality
3.2 Device Configuration
46
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...