51V Voltage-Dependent Overcurrent – Phase
Reference
Parameter
Value
I
set
Setting
0.05 to 2.5 ⋅ I
rated
V
set
Setting
V
Applied voltage (for operate time)
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI;
DTL
Tm
Time multiplier setting
0.025 to 1.6
t
delay
Delay setting
0 to 20 s, Δ 0.01 s
t
reset
Reset setting
ANDI decaying, 0 to 60 s
Operate and Reset Level
Attribute
Value
I
op
Operate level
105 % I
set
: ± 4 % or ± 1 % I
rated
V
op
Operate level
Reset level
≥ 95 % I
op
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
10.19
Technical Data
10.19 51V Voltage-Dependent Overcurrent – Phase
Reyrolle 7SR5, Transformer Protection Device, Device Manual
485
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...