Parameter:
79 Delayed Inhibit
•
Default setting:
No
The autoreclose scheme sequence may require that some selected protection elements are only used for
the first trip(s) of the sequence, typically instantaneous ungraded protection elements, before reverting
to graded protection.
This setting is used to inhibit 50G operation when it is parameterized as instantaneous and only delayed
tripping is required. This should be selected to the default setting
Off
unless required by the autoreclose
sequence.
Parameter Value
Description
No
The earth fault element is normally active and is not
blocked by autoreclose sequence requirements.
Yes
The 50G element will be inhibited from the autore-
close logic as required by the applied sequence. Incor-
rect configuration can result in no protection being
enabled.
Settings Example
There should be little or no current flowing to earth in a healthy system so earth fault relays can be given far
lower pickup levels than relays which detect current above load current in each phase conductor. Earth fault
relays are important where the fault path to earth is a high-resistance one (such as in highly arid areas) or
where the system uses high values of earthing resistor/reactance as any earth fault current that flows in the
phase conductors will be limited.
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
50G Earth Fault
Enabled
Disabled
Disabled
Functions > Protection > 50G > Gn 50G-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Measurement
RMS
Fundamental
RMS
Dir. Control
STET
Non-Dir
Setting
0.005 to 2.5 I
rated
, Δ 0.005
I
rated
2.55 to 25 I
rated
, Δ 0.05 I
rated
0.5 ⋅
I
rated
Delay
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
VTS Action
Off
Inhibit
Non-Dir
Off
5.12.5
Protection and Automation Functions
5.12 50G Instantaneous Earth Fault – Measured
218
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...