background image

 

 

 

 

 

 

 

 

 

     

 

Daikin

 

Control

 

Module

 

 

Commercial

 

(SKY)

 

and

 

industrial

 

(VRV)

 

series

 

ZN1CL

 

 

KLIC

DI

   

                

 

 

                                            

Technical

 

Note:

 

Installation

 

Note

 

 

 

© Zennio Avance y Tecnología S.L.                         Edition 2                           For further information 

www.zennio.com

           

Page. 

1

 of 

 

INTRODUCTION 

KLIC-DI

 is an interface that allows a bidirectional communication between a KNX domotic system and the commercial 

air-conditioning units of the series Sky Air and VRV systems manufactured by Daikin. 

This device controls all basic functionalities of this type of air conditioning machines as well as it handles Daikin error 
codes and communication errors that may arise. 

MASTER CONTROL VS. SLAVE CONTROL 

The great majority of internal units of SKY and VRV systems are controlled with a wired control that is connected to 
the terminal P1/P2 available in these units.  

KLIC-DI is compatible with the use of wired controls. Nevertheless, it is important to establish one of these controls as 
master control and the other as slave control. This way, if the wired control is the master, KLIC-DI must be configured 
as slave in the parameterization of the device and vice versa, if the KLIC-DI is the master control, the wired control 
must be configured as slave. 

Note: For configuring the Daikin wired control as master or slave: remove the casing 
of the control, locate the switch marked as M/S (master/slave) in the PCB and select 
the position of the switch. This switch is usually located in the lower left-hand corner 
or in the upper right-hand corner. It is necessary to remove the bus and connect it 
again in order to set the new configuration. 

It is hardly recommended to check the configuration of the wired control when 
carrying out the installation. 

 

 

INSTALLATION 

KLIC-DI is a device of reduced dimensions (90 x 60 x 35 mm) with two terminals for integrating air conditioning 
machines of the series SKY and VRV from Daikin in a KNX domotic system: 
 

 

EIB connector

, for its connection to KNX system 

bus. 

 

P1/P2 terminal

, for its connection to air- 

conditioning internal unit through a 2-wired cable 
with cross-section area lower than 0.75mm

2

 

 

 

This device does not require any external power supply, since it is fed through the KNX bus. 

For installing the KLIC-DI, the device must be connected to KNX bus, through the EIB connector, in the same way as 
any KNX device.  

Nr 

Description 

1 EIB 

connector 

Programming and checking LED. For more 
information about the color code, look up the 
manual  

3 Programming 

button 

2-wire communication terminal 

Отзывы: