Functions > Protection > 49 > Gn 49-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Char
IEC
User
IEC
Time Constant
1 to 1000 min, Δ 0.5 min
10 min
Capacity Alarm
Disabled
Enabled
Disabled
Capacity Alarm Setting
50 to 100 %, Δ 1 %
50 %
IEC 61850 Functional Information Mapping
A49PTTR*.Mod
Information
49 Thermal Overload Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A49PTTR*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A49PTTR*.Health
Information
Device Healthy
0
1
A49PTTR*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
A49PTTR*.Op
Information
Element Operated
0
1
A49PTTR*.Op.general
0
1
5.10.6
Protection and Automation Functions
5.10 49 Thermal Overload Protection
202
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...