Fault Storage Settings
Parameter:
Fault Storage > Max Fault Rec Time
•
Default Setting:
2 s
Sets the time period from fault trigger during which the operation of any LEDs is recorded.
i
i
NOTE
To achieve accurate instrumentation values for the fault records when testing, ensure a drop off delay is
applied to the test set so that the injected quantities remain on for a short duration, typically 20 ms, after
the relay has issued the trip output. This extended period of injection simulates the behavior of the power
system where faulted conditions are present until CB operation.
Parameter:
Fault Storage > Clear Faults
•
Default Setting:
This is used to delete all stored fault records.
The faults can also be deleted from a binary input or communication command.
Configuration > Data Storage > Fault Storage
Parameter
Range
Default Setting
Max fault rec time
0 to 20 s, Δ 0.01 s
20.1 to 60 s, Δ 0.1 s
Clear faults
Yes, no
No
IEC 61850 Functional Information Mapping – Last Trip Current & Voltage (VI_RFLT1)
VI_RFLT1.Mod
Information
Reset Device
x
VI_RFLT1.Mod.stVal
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
VI_RFLT.Health
Information
Device Healthy
0
1
VI_RFLT1.Health.stVal
3
1
Device Functionality
3.6 Data Storage
Reyrolle 7SR5, Transformer Protection Device, Device Manual
115
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...