Parameter:
Element
•
Default setting:
Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. These settings can be used to select the number of elements required.
Parameter:
47
‑
n Input Selection
•
Default setting: NPS (V
2
)
Parameter Value
Description
PPS (V
1
)
Positive sequence can be used to detect underlying overvoltage on the system.
This measurement is immune to distortion of voltage values due to imbalance.
NPS (V
2
)
Negative sequence can be used to detect unbalance between phases. Unbal-
anced voltage gives rise to unbalanced current flows.
ZPS (V
0
)
Zero sequence is a measurement of residual voltage. This drives current in
through the neutral or system earth connections.
Parameter:
Setting
•
Default setting:
20 V
This is the pickup threshold of the element and is compared against the respective sequence voltage. For
PPS (V
1
) this would usually set at a level higher than rated system voltage or lower if the overvoltage
element is to be used in logic to provide positive sequence undervoltage monitoring. For negative or zero
phase sequence voltages this is usually set at a lower level because there voltages are negligible during
normal system running conditions. For earth fault or residual voltage detection the setting is in zero
phase sequence volts (ZPS) and therefore 1/3 of the residual voltage (3V
0
). The elements should be set to
suit the individual application.
Parameter:
Hysteresis
•
Default setting:
3 %
The element will reset when the voltage recovers to the 47-n setting minus the 47-n hysteresis setting.
The default setting of 3 % is generally enough to avoid chatter of the element but care may be required
for settings which are close to the nominal value when set to PPS (V
1
) otherwise the element may not
reset when the voltage recovers to nominal value as the voltage is still in the hysteresis window.
Parameter:
Delay
•
Default setting:
1 s
This is the time delay setting for the DTL element. This should be set to suit the individual application.
Parameter:
VTS Inhibit
•
Default setting:
No
This setting defines the effect of a voltage transformer failure on the operation of each 47-n function
element. If a VT failure is detected by the separate VTS element, operation of the 47-n element will be
blocked if this setting is set to
Yes
. If this setting is set to
No
, the 47‑n element is unaffected by the VTS
element operation and the 47‑n element may operate on the erroneous voltage caused by the VT fuse
failure. It is generally recommended that a setting of
Yes
is beneficial if the input selection is set to
NPS
or
ZPS
.
Protection and Automation Functions
5.9 47 Sequence Overvoltage Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
195
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...