Parameter:
En Counter Reset Time
•
Default Setting:
Where
En Counter Reset Time
elapses without further count increments the count value is reset to
zero.
Settings Example
E1= I1.!I2: Equation 1 = Binary Input 1 AND NOT Binary Input 2 The output of E1 is set to
true
when the
conditions of the equation are met.
Settings Menu
Configuration > Quicklogic
Parameter
Range
Default Setting
Quick logic
Enabled
Disabled
En Equation
Enabled
Disabled
En =
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, ( , ), >,
^, !, ., In, Fn, Ln, On, Vn
En Pickup delay
0 to 14400 s
0 s
En Dropoff delay
0 s
En Counter target
1 to 999
1
En Counter reset mode
Off, Single Shot, Multi Shot
Off
En Counter reset time
0 to 14400 s
0 s
IEC 61850 Functional Information Mapping
EGGIO1.Mod
Information
Reset Device
x
EGGIO1.Mod.stVal
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
EGGIO1.Health
Information
Device Healthy
0
1
EGGIO1.Health.stVal
3
1
3.8.5
3.8.6
Device Functionality
3.8 Quick Logic
130
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...