Operate and Reset Level
Attribute
Value
V/f
op
Operate level
100 % ⋅ V/f
set
: ± 2 % or ± 0.02
Reset level
≥ 97 % of V/f
op
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
500 ms ± 300 ms
t
op
Operate time following delay
t
basic
+ t
delay
± 1 % or ± 2 s
Repeatability
± 1 %
Disengaging time
< 250 ms
Technical Data
10.3 24 Overexcitation Protection
460
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019