Functions > Protection > 74 > Gn 74-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element 1
Enabled
Disabled
Disabled
Delay 1
0 to 60 s, Δ 0.02 s
0.4 s
Element 2
Enabled
Disabled
Disabled
Delay 2
0 to 60 s, Δ 0.02 s
0.4 s
Element 3
Enabled
Disabled
Disabled
Delay 3
0 to 60 s, Δ 0.02 s
0.4 s
Information List
Input/Output Matrix
General
Pickup
User Logic
Type
IEC
60870-5-1
03
DNP3
MODBUS
RTU
74TC-1
Input
74TC-2
Input
74TC-3
Input
A74TC-1 Inhibit
Input
A74TC-2 Inhibit
Input
A74TC-3 Inhibit
Input
74TC-1
74TC-1 Operated
Output
74TC-2
74TC-2 Operated
Output
74TC-3
74TC-3 Operated
Output
Trip Circuit
Fail Operated
Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
6.5.6
Supervision Functions
6.5 74TC Trip-Circuit Supervision
364
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...