Parameter list
05.05
11-148
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Filtering of the input signals
U534
(2534)
*
S00
(B180...
B189)
Source for variable filtering time for the input signal
[SW 1.8 and later]
The content of the selected connector acts as filtering time for the PI
controller after multiplication with U535.
0 = Connector K0000
1 = Connector K0001
etc.
i001: variable filtering time
PI controller 1
i002: variable filtering time
PI controller 2
...
i010: variable filtering time
PI controller 10
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
off-line
U535
(2535)
S00
(B180...
B189)
Filtering time
for the input signal
[SW 1.8 and later]
i001: filtering time
PI controller 1
i002: filtering time
PI controller 2
...
i010: filtering time
PI controller 10
0 to 10000
[ms]
1
Ind: 10
FS=0
Type: O2
P052 = 3
P051 = 40
on-line
Controller parameters
U536
(2536)
*
S00
(B180...
B189)
Source for variable P gain
[SW 1.8 and later]
The content of the selected connector acts as the P gain for the PI controller
after multiplication with U537.
0 = Connector K0000
1 = Connector K0001
etc.
i001: variable P gain
PI controller 1
i002: variable P gain
PI controller 2
...
i010: variable P gain
PI controller 10
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
off-line
U537
(2537)
S00
(B180...
B189)
PI controller P gain
[SW 1.8 and later]
i001: P gain
PI controller 1
i002: P gain
PI controller 2
...
i010: P gain
PI controller 10
0.10 to 200.00
0.01
Ind: 10
FS=3.00
Type: O2
P052 = 3
P051 = 40
on-line
U538
(2538)
*
S00
(B180...
B189)
Source for variable Integration time
[SW 1.8 and later]
The content of the selected connector acts as the integration time for the PI
controller after multiplication with U539.
0 = Connector K0000
1 = Connector K0001
etc.
i001: variable Integration time PI controller 1
i002: variable Integration time PI controller 2
...
i010: variable Integration time PI controller 10
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
off-line
U539
(2539)
S00
(B180...
B189)
PI controller integration time
[SW 1.8 and later]
i001: Integration time
PI controller 1
i002: Integration time
PI controller 2
...
i010: Integration time
PI controller 10
0.010 to 10.000
[s]
0.001
Ind: 10
FS=3.000
Type: O2
P052 = 3
P051 = 40
on-line
Control bits
U540
(2540)
*
S00
(B180...
B189)
Freeze P component
[SW 1.8 and later]
0
Controller P component frozen (i.e. pure I controller)
1
Controller P component active
i001: PI controller 1
i002: PI controller 2
...
i010: PI controller 10
0 to 1
1
Ind: 10
FS=1
Type: O2
P052 = 3
P051 = 40
off-line
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......