05.05
Start-Up
SIEMENS AG 6RX1700-0AD76
7-19
SIMOREG DC Master Operating Instructions
Calculation of armature circuit resistance P110 from measured armature current and
armature voltage values
−
Increase the main setpoint (displayed at r001) slowly until the actual armature current
value (r019 in % of rated converter armature current) reaches approximately 70% of the
rated motor armature current.
−
Read out r019 (actual armature current value) and convert to amps (using P100)
−
Read out r038 (actual armature voltage in volts)
−
Calculate the armature circuit resistance:
amps)
to
(converted
r019
r038
[W]
R
A
=
−
Set the armature circuit resistance in parameter P110
Calculation of armature circuit inductance P111 from measured armature current at
transition from discontinuous to continuous current
−
Make an oscilloscope trace of the armature current (e.g. at terminal 12)
Increase the main setpoint (displayed at r001) slowly starting from 0 until the armature
current reaches the transition from discontinuous to continuous current.
−
Measure armature current at transition (at standstill EMF=0) I
LG, EMF=0
or read out the
value of r019 and convert to amps using P100.
−
Measure the phase-to-phase voltage of the armature power section Usupply or read out
the value of r015.
−
Calculate the armature circuit inductance using the following formula:
[A]
I
[V]
U
0.4
[mH]
L
EMF
LG,
supply
A
=
∗
=
−
Set the armature circuit inductance in parameter P111.
7.6.2
Manual setting of field circuit resistance RF (P112)
•
Rough estimation of field circuit resistance R
F
(P112) from motor rated field data
(P102)
current
field
motor
Rated
voltage
field
motor
Rated
R
F
=
•
Adapt the field circuit resistance R
F
(P112) using a field current setpoint/actual value
comparison
−
Set
parameter
P112=0
to produce a 180° field precontrol output, and thus an actual field
current value = 0
−
Set
parameter
P082=3
to ensure that the field remains permanently energized, even when
the line contactor has dropped out
−
Set
parameters
P254=0
and
P264=0,
i.e. only field precontrol active and field current
controller disabled
−
Set
parameter
P102
to the rated field current
−
Increase
parameter
P112
until the actual field current (r035 converted to amps be means of
r073.002) is equal to the required setpoint (P102).
−
Reset
parameter
P082
to the plant operating value.
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......