Parameter list
05.05
11-168
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.87 Configuring the EB2 expansion board
n773
(2773)
(Z118)
(Z119)
Display of status of binary inputs and outputs on EB2
[SW 1.5 and later]
Representation on operator panel (PMU):
3
2
1
0
4
5
Segment ON:
Corresponding terminal is activated
(HIGH level is applied)
Segment OFF:
Corresponding terminal is not activated
(LOW level is applied)
Segment or bit
0 ........ Terminal 53
1 ........ Terminal 54
2 ........ Terminal 39
3 ........ Terminal 41
4 ........ Terminal 43
5 ........ Terminal 45
i001: Terminal states of first EB2
i002: Terminal states of second EB2
Ind:
2
Type: V2
P052 = 3
U774
(2774)
*
(Z118)
(Z119)
Source for output values at binary outputs on EB2
[SW 1.5 and later]
Selection of binectors to be applied to binary outputs at terminals 39 - 46.
0 = binector B0000
1 = binector B0001
etc.
i001: BO1 of the first EB2
i002: BO2 of the first EB2
i003: BO3 of the first EB2
i004: BO4 of the first EB2
i005: BO1 of the second EB2
i006: BO2 of the second EB2
i007: BO3 of the second EB2
i008: BO4 of the second EB2
All binector numbers
1
Ind: 8
FS=0
Type: L2
P052 = 3
P051 = 40
Online
U775
(2775)
*
(Z118)
(Z119)
Signal type of analog input on EB2
[SW 1.5 and later]
0 = voltage input 0 to
±
10 V
1 = current input 0 to
±
20 mA
i001: AI1 of the first EB2
i002: AI1 of the second EB2
0 to 1
1
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Online
U776
(2776)
(Z118)
(Z119)
Normalization of analog input on EB2
[SW 1.5 and later]
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
The following general rule applies:
With a voltage input:
U
V
Y
X
776
10
[%]
=
∗
X .. input voltage in volts
Y .. % value which is generated for input
voltage
X
With a current input:
U
mA
Y
X
776
20
[%]
=
∗
X .. input current in mA
Y .. % value which is generated for input
current
X
i001: AI of the first EB2
i002: AI of the second EB2
-1000.0 to 1000.0
[%]
0.1%
Ind: 2
FS=100.0
Type: I2
P052 = 3
P051 = 40
Online
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......