SIMOREG DC Master Operating Instructions
P445 = 1:
Edge triggering of "Switch-on command of ON / OFF1":
The switch-on command is stored on the 0
→
1 transition (see Section 8, Sheet G130).
The binector selected in P444 must be in the log. "1" state. The memory is reset when
this binector switches to the log. "0" state.
In the following example circuit, the ON key (NO contact) is connected to terminal 37 and the
shutdown key (NC contact) to terminal 36. Connector K3003 (= Receive data from 1
st
CB/TB, word 3)
is used as control word 1.
The following parameter values must be set:
P444=10
Connects binector 10 (= status of terminal 36) to the reset input of the memory for the ON
signal (and to the reset input of the memory for the CRAWL command)
P445=1
Selects edge triggering of "Switch-on command of ON / OFF1" (and injection of the
crawling setpoint)
P648=3003 Connector K3003 is assigned status of control word 1.
The combination of the control bit for ON/OFF from the DPRAM control word (K3003.bit0 in this
example) and the switch-on command from the converter terminal is shown in the boxes with dot-dash
line borders.
P24_S
34
24V
5V
36
M
M
35
24V
5V
37
M
B0010
.01
.02
.03
D Q
R
1
1
1
0
<1>
&
D Q
R
1
1
≥
1
≥
1
0
1
≥
....
<1>
P440 (0)
B
B
B
P444.B (0)
B
P445 = 1
P654.B (1)
B
10
1
≥
P648.B (9)
K
3003
1
≥
&
9
=9
/
1
P648
CUD1
Switch-on / shutdown
Selection for
shutdown
Selection for
switch-on / shutdown
Select
injection of
crawing setpoint
Level /
Edge
Bit No.
0=OFF1
, Shutdown
1=ON, op. cond.
Meaning
(When P648 = 9 bit-serial
input of control bits)
Switch-on c.
of ON/OFF1
ON
Shut-
down
Control word 1
Switch-on comm.
of ON/OFF1
Control
word
bit 0
Section 8, Sheet G110
Section 8, Sheet G130
Section 8, Sheet G180
Bit 0
Bit 1
K3003.bit0
Sequence of operations for switching on drive:
1.
Enter the "Switch-on" command (e.g. via terminal "Switch-on/shutdown”)
2.
The converter exits operating state 07
3.
The "Line contactor closed" relay picks up
4.
The field current reduction command is cancelled
If "Enable operation" signal is applied:
5.
With a positive brake release time (P087), output signal "Release holding or operating brake"
(binector B0250 = 1) and wait for P087 in operating state 01.0,
with a negative brake release time (PO87 negative), go to step 6 immediately, brake remains
closed (binector B0250 = 0)
6.
Ramp-function generator, n controller and I controller are enabled
7.
When a negative brake release time (P087) has run down, output signal "Release holding or
operating brake" (binector B0250 = 1).
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......