6.1.3 Information on line-side harmonics generated by converters in a
fully-controlled three-phase bridge circuit configuration B6C and (B6)A(B6)C
Converters for the medium power range usually consist of fully-controlled three-phase bridge
circuit configurations. An example of the harmonics generated by a typical system configuration for
two firing angles (
α
= 20° and
α
= 60°) is given below.
The values have been taken from an earlier publication entitled "Harmonics in the Line-Side
Current of Six-Pulse Line-Commutated Converters" written by H. Arremann and G. Möltgen,
Siemens Research and Development Dept., Volume 7 (1978) No. 2,
©
Springer-Verlag 1978.
Formula have been specified with which the short circuit power
S
K and armature inductance
L
a of
the motor to which the specified harmonics spectrum applies can be calculated depending on the
applicable operating data [line voltage (no-load voltage
U
v0), line frequency
f
N and DC current
I
d].
A dedicated calculation must be performed if the actual system short circuit power and/or actual
armature reactance deviate from the values determined by this method.
The spectrum of harmonics listed below is obtained if the values for short circuit power
S
K at the
converter supply connection point and the armature inductance
L
a of the motor calculated by the
following formula correspond to the actual plant data. If the calculated values differ, the harmonics
must be calculated separately.
a.)
α
= 20°
b.)
α
= 60°
Fundamental factor
g
= 0.962
Fundamental factor
g
= 0.953
ν
I
ν
/
I
1
ν
I
ν
/
I
1
ν
I
ν
/
I
1
ν
I
ν
/
I
1
5 0.235 29 0.018
5 0.283 29 0.026
7 0.100 31 0.016
7 0.050 31 0.019
11 0.083 35 0.011
11 0.089 35 0.020
13 0.056 37 0.010
13 0.038 37 0.016
17 0.046 41 0.006
17 0.050 41 0.016
19 0.035 43 0.006
19 0.029 43 0.013
23 0.028 47 0.003
23 0.034 47 0.013
25 0.024 49 0.003
25 0.023 49 0.011
The fundamental-frequency current
I
1 as a reference quantity is calculated by the following
equation:
d
1
0.817
I
I
×
×
=
g
where
I
d
DC current of operating point under investigation
where
g
Fundamental factor (see above)
The harmonic currents calculated from the above tables are valid
only
for
I.) Short-circuit power
S
K at converter supply connection point
( )
S
U
X
K
v 0
2
N
VA
=
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......