05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-79
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P745
(G113)
Filtering time for "Main actual value" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard.
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P746
*
(G113)
Source for enabling of "Main actual value" analog input
Selection of binector to control
enabling of the analog input
("1" state =
enabled)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.39 Analog
outputs
(see also Section 8, Sheets G115 and G116)
Analog output terminals 12 / 13
(actual current display)
P749
*
(G115)
Control word for terminal 12 (actual current display)
0
Output with correct sign
(positive voltage: Current in torque direction MI)
(negative voltage: Current in torque direction MII)
1
Output of absolute value (positive voltage only)
2
Output with sign, inverted
(positive voltage: Current in torque direction MII)
(negative voltage: Current in torque direction MI)
3
Output of absolute value, inverted (negative voltage only)
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Analog output terminals 14 / 15
P750
*
(G115)
Source for output value at analog output 1
Selection of connector whose value is to applied to the analog output
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Online
P751
*
(G115)
Mode of signal injection at analog output 1
0 = Injection of signal with correct sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P752
(G115)
Filtering time for analog output 1
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P753
(G115)
Normalization of analog output 1
y V
x
P
[ ]
%
= ∗
753
100
x = Normalization input (corresponds to filtering output)
y = Normalization output (corresponds to output voltage at analog output
with offset = 0)
-200.00 to 199.99
[V]
0.01V
Ind: None
FS=10.00
Type: I2
P052 = 3
P051 = 40
Online
P754
(G115)
Offset for analog output 1
-10.00 to 10.00
[V]
0.01V
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
Analog output terminals 16 / 17
P755
*
(G115)
Source for output value at analog output 2
Selection of connector whose value is to applied to the analog output
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Online
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......