Faults / Alarms
05.05
10-14
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
4
The armature circuit inductance (P111) cannot be determined from the sampled values of the armature current and line
voltage of the armature current crest last generated
Possible cause:
•
P100 (IA,motor) or r072.i002 (IA,rated) very much smaller than actual motor rated current of the armature
•
LA >327.67mH (armature circuit inductance too large)
•
P100 (IA,motor) very much smaller than r072.i002 (IA,rated)
•
Armature circuit short-circuited
5
Offset adjustment of actual field current sensing is not possible
(value detected for P825 is outside permissible value range)
Possible cause:
•
Fault in actual field current sensing circuit
(defective A7004 gating board or A7001 electronics board)
7
The field circuit resistance (P112) is indeterminable
(the actual field current does not reach the internally specified setpoint of 95% of P102 as a result of P112 variation)
Possible cause:
•
RA >3276.7
Ω
•
Fault in actual field current sensing circuit (defective gating board or A7001 electronics board)
•
The command “Inject standstill field” is applied
•
P102 is set too high
•
A thyristor in the field bridge is not firing
8
80% of rated EMF (K287=P101 – P100 * P110) cannot be reached within 15s (or maximum of the three set acceleration
times)
Possible cause:
•
Acceleration time (P303, P307, P311) is set too low
•
P101 does not match the set maximum speed (UA at nmax
< P101) or setting for P102 is too low
•
The command “Ramp-function generator enable”=0 or ”Ramp-function generator stop”=1
9
Field current control loop is not stable enough to record field characteristics
(30s after injection of internal field current setpoint, actual field current is deviating by more than (0.39% of P102 + 0.15 %
of r073.002) from the setpoint)
Possible cause:
•
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
10 Field
characteristic is not uniform
(i.e. in spite of field current setpoint reduction, the flux values of this measuring point calculated from EMF and actual speed
are rising)
Possible cause:
•
High armature reaction and sharp load variations during recording of field characteristics
•
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
11
A lower field current limit of
≥
50% of P102 (IF,motor) is applied
(for this reason, it is not possible to plot a minimum of 9 field weakening measuring points)
Possible cause:
•
P103
≥
50% of P102
Check P614 !
12
The drive has reached the positive torque limit even though the applied field current setpoint is still
≥
50% of P102
(IF,motor)
Possible cause:
•
Armature current is very “unsteady”, e.g. due to high speed controller P gain setting in P225 (on drive with high integral-
action time). In this case, setting a lower actual speed filtering value in P200 and execution of another speed controller
optimization run (P051=26) may help.
•
Check torque limits
13
The drive has reached the positive armature current limit even through the applied field current setpoint is still
≥
50% of
P102 (IF,motor)
Possible cause:
•
Armature current is very “unsteady”, e.g. due to high speed controller P gain setting in P225 (on drive with high integral-
action time). In this case, setting a lower actual speed filtering value in P200 and execution of another speed controller
optimization run (P051=26) may help
•
Check armature current limits
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......