Connections
05.05
6-22
Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
6.3.2 Parameterization of SIMOREG converters for parallel connection
6.3.2.1 Standard operating mode
Master Slaves
U800 = 1
Paralleling interface active
U800 = 2
if a SIMOREG CCP is
used
U800 = 2
Paralleling interface active
Use master firing pulses
U803 = 0
"N+1 mode" not active
U804.01 = 30 control word 1
U804.02 = 31 control word 2
U804.03 = 167 Actual speed value
U804.01 = 32 status word 1
U805 = 1
(bus termination)
on the two end units
(at both physical ends of the bus cable)
0
(no bus termination) on all other units
U806 = 12
master for one slave
13
master for 2 slaves
14
master for 3 slaves
15
master for 4 slaves
16
master for 5 slaves
Set U806.02 like U806.01
U806 = 2
1 slave
U806 = 2 and 3
2 slaves
U806 = 2, 3 and 4
3 slaves
U806 = 2,3,4 and 5
4 slaves
U806 = 2,3,4,5 and 6
5 slaves
Set U806.02 like U806.01
P082 <> 0
operating mode for field
P082 = 0
internal field is not used
Set P083 depending on the source of the
actual speed value
P083 = 4
Freely connected actual speed value
P609 = 6023 Use actual speed value of master
P100 =
units
SIMOREG
of
Number
current
motor
Rated
P100
=
units
SIMOREG
of
Number
current
motor
Rated
Set P648, P649 depending on the source
of the control word
P648 = 6021 Use control word 1 from master
P649 = 6022 Use control word 2 from master
P821.01 = 31 Suppress alarm A031
P110 = Actual armature resistance
x no. of SIMOREG converters
P111 = Actual armature inductance
x no. of SIMOREG converters
The optimization run for current controller
and precontrol (P051 = 25) sets these
parameters correctly.
P110 = set as on master
P111 = set as on master
For further details about the operating principle of parallel connections between SIMOREG
converters, please refer to Section 8, Function Diagrams, Sheet G195 (paralleling interface).
Notes:
•
Control commands "Switch-on/Shutdown", "Enable operation", "Emergency stop" etc. must be
connected to a group of parallel-connected SIMOREG converters via the master device.
Terminals 37 and 38 must be permanently connected to terminal 34 on the slave !
•
Optimization runs must be started on the master device. All slaves must be connected and
ready to run when optimization is started.
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......