Function descriptions
05.05
9-26
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
USS protocol: Brief start-up guide for 6RA70 converters
G-SST1
RS232 / RS485
G-SST1
RS485
for connection of an OP1S
G-SST2 / G-SST3
RS485
Select USS protocol
P780 = 2
P780 = 2
P790 / P800 = 2
Baud rate
P783 = 1 to 13, corresponding to
300 to 187500 baud
P783 = 6 (9600 Bd) or
7 (19200 Bd)
The baud rate setting must be
identical for every node in bus
operation
P793 / P803 = 1 to 13,
corresponding to 300 to 187500
baud
No. of process data (PZD No.)
(applies to Receive and Send)
P781 = 0 to 16
P781 = 2
P791 / P801 = 0 to 16
PZD assignment for control word
and setpoints
(received process data)
All received process data are
taken to connectors and must be
wired up as required
If the control bits from the OP1S
are to be used:
Word 1 (connector K2001):
Wiring up of control bits
from OP1S, see Sec. 7.2.2
Word 2 (connector K2002):
Not
used
All received process data are
taken to connectors and must be
wired up as required
No. of PKW
P782 =
0:
No PKW data
3 / 4: 3 / 4 PKW data words
127: Variable data length for
slave
→
master
P782 = 127 variable data length
P792 / P802 =
0:
No PKW data
3 / 4: 3 / 4 PKW data words
127:
Variable data length for
slave
→
master
PZD assignment for actual
values
(transmitted process data)
Selection of transmitted values
via P784
Word 1: P784.i01=32
(stat. word 1 K0032)
Word 2: P784.i02=0
Selection of transmitted values
via P794 / P804
Node address
P786 = 0 to 30
P786 = 0 to 30
Every node must have its own,
unique address for bus operation
P796 / P806 = 0 to 30
Telegram failure time
P787 = 0.000 to 65.000s
P787 = 0.000s
P797 / P807 = 0.000 to 65.000s
Bus termination
P785 = 0: Bus term. OFF
1: Bus term. ON
P785 = 0: Bus term. OFF
1: Bus term. ON
P795 / P805 =
0: Bus term. OFF
1: Bus term. ON
Bus / point-to-point
communication
RS232: Only point-to-point
operation
possible
RS485: Bus operation possible
Bus operation possible
Bus operation possible
2-wire / 4-wire transmission
via RS485 interface
2-wire operation is selected
automatically
2-wire operation is selected
automatically
2-wire operation is selected
automatically
Cable
Connector assignments, see
Sect. 6.8 or Sheet G170 in
Sect. 8
See operating instructions for
OP1S operator panel
Connector assignments, see
Sect. 6.8 or Sheets G171, G172
in Sect. 8
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......