Start-Up
05.05
7-32
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Example of a PZD setpoint telegram:
Using the receive identifier of the above example
Receive identifier
100
d
0064
h
1. Setpoint
40063
d
9C7F
h
control word 1
2. Setpoint
8192
d
2000
h
speed setpoint 50%
3. Setpoint
123
d
007B
h
4. Setpoint
0
d
0
h
Using the CAN BusA+ from Steinbeis, the setpoint data appear as follows (data field
length = 8 bytes, low and high bytes are shown swapped round):
Identifier Data
field
64 00
7F 9C
00 20
7B 00
00 00
ID
PZD1
PZD2
PZD3
PZD4
The following functions are also available, each allowing a maximum of 16 process data to be
transferred:
PZD Receive Broadcast
This function is used to send setpoints and control words from the master
to all slaves
on
the bus simultaneously. With this option, an identical identifier must be set on all slaves
utilizing the function. This common identifier is set in CB parameter 6 (U716). The first 4
PZDs are transferred with the value set in U716 and the second 4 PZDs with the value in
U716+1, etc.
PZD Receive Multicast
This function is used to send setpoints and control words from the master to a
group of
slaves
on the bus simultaneously. With this option, all slaves within the group using the
function must be set to an identical identifier. This group identifier is set in CB parameter 7
(U717). The first 4 PZDs are transferred with the value set in U717 and the second 4 PZDs
with the value in U717+1, etc.
PZD Receive Internode
This function is used to
receive
setpoints and control words
from another slave
, allowing
PZDs to be exchanged between drives without intervention by a CAN master. For this
purpose, the identifier of PZD Receive Internode on the receiving slave must be set to the
identifier of PZD Send on the transmitting slave. This identifier is set in CB parameter 8
(U718). The first 4 PZDs are transferred with the value set in U718 and the second 4 PZDs
with the value in U718+1, etc.
Notes regarding PZD transmission:
Control word 1 must always be transferred as the first PZD word for setpoints. If control word
2 is needed, then it must be transferred as the fourth PZD word.
Bit 10 (control by PLC) must always be set in control word 1 or else the drives will not accept
setpoints and control words.
The consistency of process data can only be guaranteed within a COB. If more than 4 data
words are needed, these must be divided among several COBs. Since drives accept the
data asynchronously, the data transferred in several COBs may not always be accepted and
processed in the same processing cycle.
For this reason, interrelated data should be transferred within the same COB. If this is not
possible, data consistency can be assured by means of control word bit 10 (control by PLC),
i.e. by setting the bit to "off" in the first COB to temporarily prevent the drive from accepting
the data from the communications board. The remaining data are then transmitted. Finally, a
COB containing a control word bit 10 set to "on" is transmitted. Since a drive can accept up
to 16 PZDs simultaneously from the communication board, data consistency is assured.
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......