Function descriptions
05.05
9-36
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Basic tasks for configuring periodic overload operation
Terms:
Base-load duty period
300
= min. base-load duty period for 300 s cycle time
Overload period
300
= max. overload period for 300 s cycle time
Basic task 1:
Known quantities: Converter type, cycle time, overload factor, overload period
Quantities to be found: Minimum base-load duty period and maximum base-load current
Solution:
Selection of limit characteristic for specified converter type and overload factor
Cycle time < 300s: Overload period
300
= (300s/cycle time) * overload period
Cycle time
≥
300s: Overload period
300
= Overload period
If: Overload period
300
> overload period
300
for base-load current = 0
Then: Required load cycle cannot be configured,
Otherwise: Determine the maximum base-load current for overload period
300
from the
limit characteristic
Example 1:
Known quantities: 30A/4Q converter; cycle time 113.2s; overload factor = 1.45; overload period = 20s
Quantities to be found: Minimum base-load period and maximum base-load current
Solution:
Limit characteristic for 30A/4Q converter, overload factor 1.5
Overload period
300
= (300s/113.2s) * 20s = 53s
Base-load period
300
= 300s – 53s = 247s
→
Maximum base-load current = approx. 45% of I
rated
= 13.5A
Basic task 2:
Known quantities: Converter type, cycle time, overload factor, base-load current
Quantities to be found: Minimum base-load period and maximum overload period
Solution:
Selection of limit characteristic for specified converter type and overload factor
Determine overload period
300
for base-load current from limit characteristic
Cycle time < 300s:
Max. overload period = (cycle time/300s) * overload period
300
Min. base-load period = cycle time – max. overload period
Cycle
time
≥
300s:
Max. overload period = overload period
300
Min. base-load period = cycle time – max. overload period
Example 2:
Known quantities: 30A/4Q converter; cycle time 140s; current overload factor = 1.15;
base-load current = 0.6*I
rated
= 18A
Quantities to be found: Minimum base-load period and maximum overload period
Solution:
Limit characteristic for 30A/4Q converter, overload factor 1.2
Base-load current = 60% of I
rated
→
overload period
300
= 126.35s
Max. overload period = (140s/300s) * 126.35s = approx. 58s
Min. base-load period = 140s – 58s = 82s
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......