05.05
Connectors and binectors
SIEMENS AG 6RX1700-0AD76
12-27
SIMOREG DC Master Operating Instructions
12.2 Binector
list
The states of binectors can be displayed via parameters r045 and P046.
Binector
Name, description
Function
diag., Sheet
Fixed values
B0000
Fixed value 0
G120
B0001
Fixed value 1
G120
Binary inputs, terminals 36 to 43
B0010
Status of terminal 36
G110
B0011
Status of terminal 36, inverted
G110
B0012
Status of terminal 37
G110
B0013
Status of terminal 37, inverted
G110
B0014
Status of terminal 38
G110
B0015
Status of terminal 38, inverted
G110
B0016
Status of terminal 39
G110
B0017
Status of terminal 39, inverted
G110
B0018
Status of terminal 40
G111
B0019
Status of terminal 40, inverted
G111
B0020
Status of terminal 41
G111
B0021
Status of terminal 41, inverted
G111
B0022
Status of terminal 42
G111
B0023
Status of terminal 42, inverted
G111
B0024
Status of terminal 43
G111
B0025
Status of terminal 43, inverted
G111
B0032
No meaning
B0033
No meaning
B0034
No meaning
B0035
No meaning
Binary inputs, terminals 211 to 214 / motor interface
B0040
Status of terminal 211 / Brush length monitor (binary) (0=fault)
G186
B0041
Status of terminal 211, inverted
G186
B0042
Status of terminal 212 / Bearing condition monitor (binary) (1=fault)
G186
B0043
Status of terminal 212, inverted
G186
B0044
Status of terminal 213 / Motor fan monitor (binary) (0=fault)
G186
B0045
Status of terminal 213, inverted
G186
B0046
Status of terminal 214 / Motor temperature monitor (binary) (0=fault)
G186
B0047
Status of terminal 214, inverted
G186
Analog inputs
B0050
Analog input, terminal 4: 1 = Open circuit (i
≤
2 mA)
G113
B0051
Analog input, terminal 6: 1 = Open circuit (i
≤
2 mA)
G113
Pulse encoder evaluation
B0052
Fault in digital speed sensing circuit
G145
B0053
Underflow of actual position value
[SW 1.9 and later]
This binector changes to 1 when connector KK0046 (actual position value extended in software to a 32-bit
value) counts from value 8000 0000H (= –2
31
) to value 7FFF FFFFH (= +2
31
–1).
Binector B0053 does not change back to 0 until connector KK0046 assumes a value other than 7FFF
FFFFH (= +2
31
–1) again.
G145
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......